Page 6 - KRJ English Catalogue
P. 6
KAT-N PIERCING CONNECTOR FOR SAFETY GROUNDING IN LOW VOLTAGE POWER NETWORK
The KAT-N connector was designed and developed with objective to allow the temporay safety grounding in low voltage Power Distribution System, in application in multiplexed power network. The connector consists of a body with two base polymeric accommodation, composed by screws fuse heads with controlled torque, four busbar tinned copper alloy with piercing teeth + latch key to grounding.
With the KAT-N connector connected to the power network, the user will assembly anytime the protective grounding in reliable and safety way, through the hot stick, performing connection of the latch key, connecting the latch key that rotating it until turn it locked, performs the grounding of the phases in the neutral.
KLOK TERMINAL ALUMINUM ALLOY WITH SUPERFICIAL FINISHING
The terminals KLOK family are manufactured in aluminum alloy with a surface finishing inhibitor of galvanic corrosion and action of maresia developed by KRJ, allowing connections with copper or aluminum, not needing special tools for application. It has a variety of applications in the industrial and electrical connections in networks having as one of its main features is reusable. The KLOK terminals are supplied with 9 models ranging from 16mm2 to 400mm2 (6 AWG to 750MCM) Can be supplied with 1 or 2 holes. Additional information is available through our Technical Product Specification.
CONNECTOR
KAT-N A
KAT-N B
MAIN CABLE (mm2)
16
70
MAIN CABLE (mm2)
95
185
TORQUE (N.m)
8-12
8-12
CABLE CLASSIFICATION TABLE
MODEL
DIAMETER RANGE (mm)
BARE CABLES (AWG/MCM)
BARE CABLES (mm2)
INSULATED CABLES (mm2)
SCREW 1
SCREW 2
SIDE FOR SMALLER CABLE (P)
SIDE FOR BIGGER CABLE (G)
SIDE FOR SMALLER CABLE (P)
SIDE FOR BIGGER CABLE (G)
SIDE FOR SMALLER CABLE (P)
SIDE FOR BIGGER CABLE (G)
SIDE FOR SMALLER CABLE (P)
SIDE FOR BIGGER CABLE (G)
KL-1
4,6 - 4,8
5,0 - 5,1
6 AAC/Cu
6 ACSR
--------------
16 AAC/Cu
16 COMP AAC/Cu
--------------
M5 X 30
--------------
KL-2
5,8 - 6,0
6,2 - 6,4
4 AAC/Cu
4 ACSR
--------------
25 AAC/Cu
25 COMP AAC/Cu
--------------
M5 X 30
--------------
KL-3
6,7 - 7,3
7,3 - 8,1
--------------
2 AAC/Cu 2 CAA
--------------
35 AAC/Cu
35 COMP AAC/Cu
50 COMP AAC/Cu
M8 X 45
--------------
KL-4
9,0 - 9,7
10,0 - 10,6
1/0 AAC/Cu
2/0 AAC/Cu 1/0 ACSR
50 AAC/Cu
70 AAC/Cu
70 COMP AAC/Cu
--------------
M10 X 60
M10 X 30
KL-5
11,2 - 12,3
12,7 - 13,3
3/0 AAC/Cu 2/0 ACSR
4/0 AAC/Cu 3/0 ACSR
95 AAC/Cu
--------------
95 COMP AAC/Cu
120 COMP AAC/Cu
M12 X 75
M12 X 35
KL-6
14,2 - 14,5
14,5 - 15,1
4/0 ACSR
266,8 AAC/Cu
--------------
120 AAC/Cu
150 COMP AAC/Cu
--------------
M12 X 75
M12 X 35
KL-7
15,4 - 17,0
17,3 - 18,9
266,8 ACSR 366,4 AAC/Cu
397,5 AAC/Cu 336,4 ACSR
150 AAC/Cu
185 AAC/Cu
185 COMP AAC/Cu
240 COMP AAC/Cu
M12 X 75
M12 X 35
KL-8
20,0 - 20,8
21,7 - 22,5
477 AAC/Cu 397,5 ACSR
556,5 AAC/Cu 477 ACSR
240 AAC/Cu
300 AAC/Cu
300 COMP AAC/Cu
350 COMP AAC/Cu
M12 X 75
M12 X 35
KL-9
22,3 - 23,7
23,8 - 25,4
636 AAC/Cu 556,5 ACSR
750 AAC/Cu 636 ACSR
--------------
350 AAC/Cu
400 COMP AAC/Cu
--------------
M14 X 90
M14 X 40
6
NOTE AAC - All aluminium conductor Cu - Bare copper cable
ACSR - Aluminium conductor steel reinforced
COMP - Compacted or insulated copper or aluminum cables
Dimensions and tolerances follow our design number 580.976 Further information at our product specification ETE-005.